 Argus-Power-System-MIB DEFINITIONS ::= BEGIN

 --==========================================================================
 -- NOTE: Refer to RFC1628 for the formal definition of the SNMPv2-SMI MIB.
 --==========================================================================

 IMPORTS
  MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE, enterprises
   FROM SNMPv2-SMI;

 argus MODULE-IDENTITY
  LAST-UPDATED "201612090000Z"
  ORGANIZATION "Alpha Technologies Ltd."
  CONTACT-INFO
      "Alpha Technologies Ltd.
     7700 Riverfront Gate
     Burnaby, BC  V5J 5M4
     Canada

     Tel: 1-604-436-5900
     Fax: 1-604-436-1233"
  DESCRIPTION
    "This MIB defines the information block(s) available in CXC RMU
     as defined by the following list: 
    - upsDevice: the CXC-series of controllers"   
    
  REVISION    "201612090000Z"  -- December 9, 2016
  DESCRIPTION
   "
   Updated upsSecondsOnBattery to upsMinutesOnBattery to match unit value of the data.
   "
    
    
 ::= { enterprises 7309 }

 PositiveInteger ::= TEXTUAL-CONVENTION
       DISPLAY-HINT "d"
       STATUS       current
       DESCRIPTION
               "This data type is a non-zero and non-negative value."
       SYNTAX       INTEGER (1..2147483647)

 NonNegativeInteger ::= TEXTUAL-CONVENTION
       DISPLAY-HINT "d"
       STATUS       current
       DESCRIPTION
               "This data type is a non-negative value."
       SYNTAX       INTEGER (0..2147483647)        
       
    DisplayString ::=
              OCTET STRING
          -- This data type is used to model textual information taken
          -- from the NVT ASCII character set.  By convention, objects
          -- with this syntax are declared as having
          --
          --      SIZE (0..255)

          PhysAddress ::=
              OCTET STRING
          -- This data type is used to model media addresses.  For many
          -- types of media, this will be in a binary representation.
          -- For example, an ethernet address would be represented as
          -- a string of 6 octets.

       
          

 
 upsPower            OBJECT IDENTIFIER ::= { argus     6}
 upsDevice   OBJECT IDENTIFIER ::= { upsPower  1} 
 upsIdent             OBJECT IDENTIFIER ::= { upsDevice 1}
 upsBattery           OBJECT IDENTIFIER ::= { upsDevice 2}
 upsInput             OBJECT IDENTIFIER ::= { upsDevice 3}
 upsOutput            OBJECT IDENTIFIER ::= { upsDevice 4}
 upsAlarm   OBJECT IDENTIFIER ::= { upsDevice 5}
 upsConfig   OBJECT IDENTIFIER ::= { upsDevice 6}
 upsTraps   OBJECT IDENTIFIER ::= { upsDevice 7}
 upsExtra   OBJECT IDENTIFIER ::= { upsDevice 8} 


 --==========================================================================
 -- Start of Extra Information
 -- Power upstem specified variables and alarm status are maintained in the extra 
 -- table. CXC RMU will populate realtime live data to these variables and 
 -- status entries in the table. Table entries' string value are configured by 
 -- CXC RMU web interface and support unicode string
 --==========================================================================

 upsExtraCount OBJECT-TYPE
  SYNTAX INTEGER (0..65535)
  MAX-ACCESS read-only
  STATUS current
  DESCRIPTION "Number of extra variables"
 ::= { upsExtra 1 }

 upsExtraTable OBJECT-TYPE
  SYNTAX SEQUENCE OF UpsExtraEntry
  MAX-ACCESS not-accessible
  STATUS current
  DESCRIPTION "A table of CXC upstem controller extra variables"
 ::= { upsExtra 2 }

 upsExtraEntry OBJECT-TYPE
  SYNTAX UpsExtraEntry
  MAX-ACCESS not-accessible
  STATUS current
  DESCRIPTION "An entry into the CXC upstem controller extra variable table"
  INDEX { upsExtraIndex }
  ::= { upsExtraTable 1 }

 UpsExtraEntry
 ::= SEQUENCE {
  upsExtraIndex INTEGER,
  upsExtraName DisplayString ,
  upsExtraIntegerValue INTEGER,
  upsExtraStringValue DisplayString
 }

 upsExtraIndex OBJECT-TYPE
  SYNTAX INTEGER (0..65535)
  MAX-ACCESS read-only
  STATUS current
  DESCRIPTION "The index of the extra variable in the CXC upstem controller table"
 ::= { upsExtraEntry 1 }

 upsExtraName OBJECT-TYPE
  SYNTAX DisplayString (SIZE(0..30))
  MAX-ACCESS read-only
  STATUS current
  DESCRIPTION "The description of the extra variable as reported by the CXC upstem controller"
 ::= { upsExtraEntry 2 }

 upsExtraIntegerValue OBJECT-TYPE
  SYNTAX INTEGER (-1000000000..1000000000)
  MAX-ACCESS read-only 
  STATUS current
  DESCRIPTION "The integer value of the extra variable as reported by the CXC upstem controller"
 ::= { upsExtraEntry 3 }

 upsExtraStringValue OBJECT-TYPE
  SYNTAX DisplayString (SIZE(0..255))
  MAX-ACCESS read-only
  STATUS current
  DESCRIPTION "The string value of the extra variable as reported by the CXC upstem controller"
 ::= { upsExtraEntry 4 }

 --==========================================================================
 -- The OBJECT IDENTIFIERs for the traps must be defined in this manner to
 -- satisfy the NetSight MIB compiler; in particular, nodes cannot be defined 
 -- concatenated in a single line, but must be defined explicitly node by node
 -- (hence, the upsDevice.upsTraps.upsTrap definition)
 -- In addition, forward references to extra upstem variables are needed for 
 -- upsTrap by CastleRock SNMPc for event filter and match features.
 --==========================================================================
 upsTrap  OBJECT IDENTIFIER ::= { upsTraps 0 }

 --==========================================================================
 -- Start of Traps
 --==========================================================================

 upsAlarmTrap NOTIFICATION-TYPE
  OBJECTS {
   upsExtraIntegerValue,
   upsExtraStringValue,
   upsExtraIndex,   
   upsExtraName
  }
  STATUS  current
  DESCRIPTION "A trap issued from a change in state in one of the Alarms on the Novus controller"
 ::= { upsTrap 1 }

 upsAgentStartupTrap NOTIFICATION-TYPE
  OBJECTS {
   upsIdentSiteName
  }
  STATUS  current
  DESCRIPTION "A trap to indicate that the agent software has started up."
 ::= { upsTrap 2 }

 upsAgentShutdownTrap NOTIFICATION-TYPE
  OBJECTS {
   upsIdentSiteName
  }
  STATUS  current
  DESCRIPTION "A trap to indicate that the agent software has shutdown."
 ::= { upsTrap 3 }

     upsAgentFaultTrap NOTIFICATION-TYPE
  OBJECTS {
   upsExtraIntegerValue,
   upsExtraStringValue,
   upsExtraIndex,   
   upsExtraName
  }
  STATUS  current
  DESCRIPTION "A trap issued from a change in state in one of the Faults on the Novus controller"
 ::= { upsTrap 4 }

    upsAgentEventTrap NOTIFICATION-TYPE
  OBJECTS {
   upsExtraIntegerValue,
   upsExtraStringValue,
   upsExtraIndex,   
   upsExtraName
  }
  STATUS  current
  DESCRIPTION "A trap issued from a change in state in one of the Events on the Novus controller"
 ::= { upsTrap 5 }


 

   --
   -- The Device Identification group.
   --      All objects in this group are set at device initialization
   --      and remain static.
   --



   upsIdentManufacturer OBJECT-TYPE
       SYNTAX     DisplayString (SIZE (0..255))
       MAX-ACCESS read-only
       STATUS     current
       DESCRIPTION
               "The name of the UPS manufacturer."
       ::= { upsIdent 1 }

   upsIdentProductCode OBJECT-TYPE
       SYNTAX     DisplayString (SIZE (0..255))
       MAX-ACCESS read-only
       STATUS     current
       DESCRIPTION
               "The UPS Model designation."
       ::= { upsIdent 2 }

   upsIdentModel OBJECT-TYPE
       SYNTAX     DisplayString (SIZE (0..255))
       MAX-ACCESS read-only
       STATUS     current
       DESCRIPTION
               "The UPS Product code designation."
       ::= { upsIdent 3 }

   upsIdentUPSSoftwareVersion OBJECT-TYPE
       SYNTAX     DisplayString (SIZE (0..255))
       MAX-ACCESS read-only
       STATUS     current
       DESCRIPTION
               "The UPS firmware/software version(s).  This variable
               may or may not have the same value as
               upsIdentAgentSoftwareVersion in some implementations."
       ::= { upsIdent 4 }

   upsIdentAgentSoftwareVersion OBJECT-TYPE
       SYNTAX     DisplayString (SIZE (0..255))
       MAX-ACCESS read-only
       STATUS     current
       DESCRIPTION
               "The UPS agent software version.  This variable may or
               may not have the same value as
               upsIdentUPSSoftwareVersion in some implementations."
       ::= { upsIdent 5 }

   upsIdentName OBJECT-TYPE
       SYNTAX     DisplayString (SIZE(0..255))
       MAX-ACCESS read-only
       STATUS     current
       DESCRIPTION
               "A string identifying the UPS.  This object should be
               set by the administrator."
       ::= { upsIdent 6 }

   upsIdentAttachedDevices OBJECT-TYPE
       SYNTAX     DisplayString (SIZE(0..255))
       MAX-ACCESS read-only
       STATUS     current
       DESCRIPTION
               "A string identifying the devices attached to the
               output(s) of the UPS.  This object should be set by
               the administrator."
       ::= { upsIdent 7 }
 
   upsIdentSiteName OBJECT-TYPE
  SYNTAX DisplayString (SIZE(0..255))
  MAX-ACCESS read-write
  STATUS current
  DESCRIPTION "Site Name"
 ::= { upsIdent 8 }

   upsIdentSiteCity OBJECT-TYPE
  SYNTAX DisplayString (SIZE(0..255))
  MAX-ACCESS read-write
  STATUS current
  DESCRIPTION "Site City"
 ::= { upsIdent 9 }

   upsIdentSiteRegion OBJECT-TYPE
  SYNTAX DisplayString (SIZE(0..255))
  MAX-ACCESS read-write
  STATUS current
  DESCRIPTION "Site Region"
 ::= { upsIdent 10 }

   upsIdentSiteCountry OBJECT-TYPE
  SYNTAX DisplayString (SIZE(0..255))
  MAX-ACCESS read-write
  STATUS current
  DESCRIPTION "Site Country"
 ::= { upsIdent 11 }

   upsIdentContactName OBJECT-TYPE
  SYNTAX DisplayString (SIZE(0..255))
  MAX-ACCESS read-write
  STATUS current
  DESCRIPTION "Contact Name"
 ::= { upsIdent 12 }

  upsIdentPhoneNumber OBJECT-TYPE
  SYNTAX DisplayString (SIZE(0..255))
  MAX-ACCESS read-write
  STATUS current
  DESCRIPTION "Phone Number"
 ::= { upsIdent 13 }

  upsIdentDate OBJECT-TYPE
  SYNTAX DisplayString (SIZE(0..255))
  MAX-ACCESS read-write
  STATUS current
  DESCRIPTION "Date of the RMU-Novus"
 ::= { upsIdent 14 }

  upsIdentTime OBJECT-TYPE
   SYNTAX DisplayString (SIZE(0..255))
  MAX-ACCESS read-write
  STATUS current
  DESCRIPTION "Time of the RMU-Novus"
 ::= { upsIdent 15 }

 
 
   --
   -- Battery Group
   --



   upsBatteryStatus OBJECT-TYPE
       SYNTAX     INTEGER {
           unknown(1),
           batteryNormal(2),
           batteryLow(3),
           batteryDepleted(4)
       }
       MAX-ACCESS read-only
       STATUS     current
       DESCRIPTION
               "The indication of the capacity remaining in the UPS
               system's batteries.   A value of batteryNormal
               indicates that the remaining run-time is greater than
               upsConfigLowBattTime.  A value of batteryLow indicates
               that the remaining battery run-time is less than or
               equal to upsConfigLowBattTime.  A value of
               batteryDepleted indicates that the UPS will be unable
               to sustain the present load when and if the utility
               power is lost (including the possibility that the
               utility power is currently absent and the UPS is
               unable to sustain the output)."
       ::= { upsBattery 1 }        
       
   upsMinutesOnBattery OBJECT-TYPE
       SYNTAX     INTEGER 
       UNITS      "minutes"
       MAX-ACCESS read-only
       STATUS     current
       DESCRIPTION
               "
               The accumulated elapsed time that the UPS system have been on battery.
               "
       ::= { upsBattery 2 }

   upsBatteryVoltage OBJECT-TYPE
       SYNTAX     INTEGER 
       UNITS      "0.1 Volt DC"
       MAX-ACCESS read-only
       STATUS     current
       DESCRIPTION
               "The magnitude of the present battery voltage."
       ::= { upsBattery 3 }

   upsBatteryChargingCurrent OBJECT-TYPE
       SYNTAX     INTEGER 
       UNITS      "0.1 Amp DC"
       MAX-ACCESS read-only
       STATUS     current
       DESCRIPTION
               "The present battery charging current."
       ::= { upsBattery 4 }

   upsBatteryCapacity OBJECT-TYPE
       SYNTAX     INTEGER 
       UNITS      "0.1 Amp DC"
       MAX-ACCESS read-only
       STATUS     current
       DESCRIPTION
               "The present battery capacity."
       ::= { upsBattery 5 }


   upsBatteryTemperature OBJECT-TYPE
       SYNTAX     INTEGER 
       UNITS      "degrees Centigrade"
       MAX-ACCESS read-only
       STATUS     current
       DESCRIPTION
               "The ambient temperature at or near the UPS Battery
               casing."
       ::= { upsBattery 6 }
   upsBatteryLowWarning OBJECT-TYPE
       SYNTAX     INTEGER 
       UNITS      "percentage"
       MAX-ACCESS read-write
       STATUS     current
       DESCRIPTION
               "The set battery capacity percentage at which the unit will raise an alarm."
       ::= { upsBattery 7 }


   --
   -- Input Group
   --


   
   upsInputNumLines OBJECT-TYPE
       SYNTAX     INTEGER 
       MAX-ACCESS read-only
       STATUS     current
       DESCRIPTION
               "The number of input lines utilized in this device.
               This variable indicates the number of rows in the
               input table."
       ::= { upsInput 1 }

   upsInputTable OBJECT-TYPE
       SYNTAX     SEQUENCE OF UpsInputEntry
       MAX-ACCESS not-accessible
       STATUS     current
       DESCRIPTION
               "A list of input table entries.  The number of entries
               is given by the value of upsInputNumLines."
       ::= { upsInput 2 }

   upsInputEntry OBJECT-TYPE
       SYNTAX     UpsInputEntry
       MAX-ACCESS not-accessible
       STATUS     current
       DESCRIPTION
               "An entry containing information applicable to a
               particular input line."
       INDEX { upsInputLineIndex }
       ::= { upsInputTable 1 }

   UpsInputEntry ::= SEQUENCE {
       upsInputLineIndex   INTEGER ,
       upsInputFrequency   INTEGER ,
       upsInputVoltage     INTEGER 
   }

   upsInputLineIndex OBJECT-TYPE
       SYNTAX     INTEGER 
       MAX-ACCESS not-accessible
       STATUS     current
       DESCRIPTION
               "The input line identifier."
       ::= { upsInputEntry 1 }

   upsInputFrequency OBJECT-TYPE
       SYNTAX     INTEGER 
       UNITS      "Hertz"
       MAX-ACCESS read-only
       STATUS     current
       DESCRIPTION
               "The present input frequency."
       ::= { upsInputEntry 2 }

   upsInputVoltage OBJECT-TYPE
       SYNTAX     INTEGER 
       UNITS      "0.1 RMS Volts"
       MAX-ACCESS read-only
       STATUS     current
       DESCRIPTION
               "The magnitude of the present input voltage."
       ::= { upsInputEntry 3 }
 
   --
   -- The Output group.
   --



   upsOutputSource OBJECT-TYPE
       SYNTAX     INTEGER {
           standby(1),
           line(2),
           boost2(3),
           boost1(4),
           buck1(5),
           buck2(6),
           inverter(7),
      retransfer(8),
      transfer(9),
      shutdown(10),
      bypass(11)
       }
       MAX-ACCESS read-only
       STATUS     current
       DESCRIPTION
               "The present source of output power.  The enumeration
               line(2) indicates that the Novus is in line mode."
       ::= { upsOutput 1 }

   upsOutputFrequency OBJECT-TYPE
       SYNTAX     INTEGER 
       UNITS      "0.1 Hertz"
       MAX-ACCESS read-only
       STATUS     current
       DESCRIPTION
               "The present output frequency."
       ::= { upsOutput 2 }

   upsOutputNumLines OBJECT-TYPE
       SYNTAX     INTEGER 
       MAX-ACCESS read-only
       STATUS     current
       DESCRIPTION
               "The number of output lines utilized in this device.
               This variable indicates the number of rows in the
               output table."
       ::= { upsOutput 3 }

   upsOutputTable OBJECT-TYPE
       SYNTAX     SEQUENCE OF UpsOutputEntry
       MAX-ACCESS not-accessible
       STATUS     current
       DESCRIPTION
               "A list of output table entries.  The number of
               entries is given by the value of upsOutputNumLines."
       ::= { upsOutput 4 }

   upsOutputEntry OBJECT-TYPE
       SYNTAX     UpsOutputEntry
       MAX-ACCESS not-accessible
       STATUS     current
       DESCRIPTION
               "An entry containing information applicable to a
               particular output line."
       INDEX { upsOutputLineIndex }
       ::= { upsOutputTable 1 }

   UpsOutputEntry ::= SEQUENCE {
       upsOutputLineIndex   INTEGER ,
       upsOutputVoltage     INTEGER ,
       upsOutputCurrent     INTEGER ,
       upsOutputPowerVA     INTEGER ,
  upsOutputPowerWatt   INTEGER ,
  upsPowerFactor     INTEGER ,
       upsOutputPercentLoad INTEGER
   }

   upsOutputLineIndex OBJECT-TYPE
       SYNTAX     INTEGER 
       MAX-ACCESS not-accessible
       STATUS     current
       DESCRIPTION
               "The output line identifier."
       ::= { upsOutputEntry 1 }

   upsOutputVoltage OBJECT-TYPE
       SYNTAX     INTEGER 
       UNITS      "0.1 RMS Volts"
       MAX-ACCESS read-only
       STATUS     current
       DESCRIPTION
               "The present output voltage."
       ::= { upsOutputEntry 2 }

   upsOutputCurrent OBJECT-TYPE
       SYNTAX     INTEGER 
       UNITS      "0.1 RMS Amp"
       MAX-ACCESS read-only
       STATUS     current
       DESCRIPTION
               "The present output current."
       ::= { upsOutputEntry 3 }

   upsOutputPowerVA  OBJECT-TYPE
       SYNTAX     INTEGER 
       UNITS      "VA"
       MAX-ACCESS read-only
       STATUS     current
       DESCRIPTION
               "The present output VA."
       ::= { upsOutputEntry 4 }

   upsOutputPowerWatt  OBJECT-TYPE
       SYNTAX     INTEGER 
       UNITS      "Watts"
       MAX-ACCESS read-only
       STATUS     current
       DESCRIPTION
               "The present output true power."
       ::= { upsOutputEntry 5 }

   upsPowerFactor     OBJECT-TYPE
       SYNTAX     INTEGER 
       UNITS      "percent"
       MAX-ACCESS read-only
       STATUS     current
       DESCRIPTION
               "The present power factor."
       ::= { upsOutputEntry 6 }

   upsOutputPercentLoad OBJECT-TYPE
       SYNTAX     INTEGER (0..200)
       UNITS      "percent"
       MAX-ACCESS read-only
       STATUS     current
       DESCRIPTION
               "The percentage of the UPS power capacity presently
               being used on this output line, i.e., the greater of
               the percent load of true power capacity and the
               percent load of VA."
       ::= { upsOutputEntry 7 }

   --
   -- The Alarms group.
   --



   upsAlarmsPresent OBJECT-TYPE
       SYNTAX     INTEGER 
       MAX-ACCESS read-only
       STATUS     current
       DESCRIPTION
               "The present number of active alarm conditions."
       ::= { upsAlarm 1 }

   upsAlarmTable OBJECT-TYPE
       SYNTAX     SEQUENCE OF UpsAlarmEntry
       MAX-ACCESS not-accessible
       STATUS     current
       DESCRIPTION
               "A list of alarm table entries. "
       ::= { upsAlarm 2 }

   upsAlarmEntry OBJECT-TYPE
       SYNTAX     UpsAlarmEntry
       MAX-ACCESS not-accessible
       STATUS     current
       DESCRIPTION
               "An entry containing information applicable to a
               particular alarm."
       INDEX { upsAlarmId }
       ::= { upsAlarmTable 1 }

   UpsAlarmEntry ::= SEQUENCE {
       upsAlarmId          INTEGER ,
       upsAlarmDescr       DisplayString,
  upsAlarmStatus    INTEGER      
   }

   upsAlarmId OBJECT-TYPE
       SYNTAX     INTEGER 
       MAX-ACCESS not-accessible
       STATUS     current
       DESCRIPTION
               "A unique identifier for an alarm condition.  This
               value must remain constant."
       ::= { upsAlarmEntry 1 }

   upsAlarmDescr OBJECT-TYPE
       SYNTAX     DisplayString (SIZE(0..255))
       MAX-ACCESS read-only
       STATUS     current
       DESCRIPTION
               "A unique description of the alarm. "
       ::= { upsAlarmEntry 2 }
  
   upsAlarmStatus OBJECT-TYPE
       SYNTAX     INTEGER      
       MAX-ACCESS read-only
       STATUS     current
       DESCRIPTION
               "1 - ON or 0 - OFF. "
       ::= { upsAlarmEntry 3 }

   --
   -- The Config group.
   --



   upsConfigLineQualifyTime OBJECT-TYPE
       SYNTAX     INTEGER 
       UNITS      "seconds"
       MAX-ACCESS read-only
       STATUS     current
       DESCRIPTION
               "This objects displays the line qualify time."
       ::= { upsConfig 1 }

   upsConfigLineOutputVoltageHighLimit OBJECT-TYPE
       SYNTAX     INTEGER 
       UNITS      "volttenth"
       MAX-ACCESS read-only
       STATUS     current
       DESCRIPTION
               "This object represents the Line output High Voltage Limit."
       ::= { upsConfig 2 }

   upsConfigLineOutputVoltageLowLimit OBJECT-TYPE
       SYNTAX     INTEGER 
       UNITS      "volttenth"
       MAX-ACCESS read-only
       STATUS     current
       DESCRIPTION
               "This object represents the Line output Low Voltage Limit."
       ::= { upsConfig 3 }

   upsConfigFanOnTemperature OBJECT-TYPE
       SYNTAX     INTEGER 
       UNITS      "degreeC"
       MAX-ACCESS read-only
       STATUS     current
       DESCRIPTION
               "This object represents the Fan on temperature."
       ::= { upsConfig 4 }


  upsShutdownStatus OBJECT-TYPE
       SYNTAX     INTEGER 
       UNITS      ""
       MAX-ACCESS read-write
       STATUS     current
       DESCRIPTION
               "This object tells us if output is disabled or enabled."
       ::= { upsConfig 5 }
  upsInverterOffDelayTime OBJECT-TYPE
       SYNTAX     INTEGER 
       UNITS      "seconds"
       MAX-ACCESS read-write
       STATUS     current
       DESCRIPTION
               "This object represents the inverter off delay time."
       ::= { upsConfig 6 }

  upsConfigIPAddress OBJECT-TYPE
       SYNTAX DisplayString (SIZE(0..255))        
       MAX-ACCESS read-write
       STATUS     current
       DESCRIPTION
               "This objects displays the IP address of the RMU."
       ::= { upsConfig 7 }

  upsConfigNetMask OBJECT-TYPE
       SYNTAX DisplayString (SIZE(0..255)) 
       MAX-ACCESS read-write
       STATUS     current
       DESCRIPTION
               "This object displays the Net Mask of the RMU."
       ::= { upsConfig 8 }

  upsConfigGateway OBJECT-TYPE
       SYNTAX DisplayString (SIZE(0..255)) 
       MAX-ACCESS read-write
       STATUS     current
       DESCRIPTION
               "This object displays the Gateway of the RMU."
       ::= { upsConfig 9 }

  upsConfigSnmpCommunity OBJECT-TYPE
       SYNTAX DisplayString (SIZE(0..255))        
       MAX-ACCESS read-write
       STATUS     current
       DESCRIPTION
               "This object displays the SNMP community"
       ::= { upsConfig 10 }

  upsConfigSnmpTrapIPDestination OBJECT-TYPE
       SYNTAX DisplayString (SIZE(0..255)) 
       MAX-ACCESS read-write
       STATUS     current
       DESCRIPTION
               "This object displays the SNMP Trap IP destination."
       ::= { upsConfig 11 }  
  
END